Vertiv UPS GXT5-1000IRT On-Line UPS Rack/Tower 1000VA/1000W
Dove Code:
UP4506 |
Manufacturer:
GXT5-1000IRT2UXL
Overview
The Vertiv™ Vertiv® GXT5 UPS is an online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system.
The Vertiv® GXT5 is a single phase UPS built on the super reliable platform of GXT series- supporting over a million critical systems all over the world.
Warranty
36 Month Return to Base Warranty
Features
- Top-level on-line double conversion UPS for mission-critical applications
- Unity output power factor
- LCD multi-language color display (gravity sensing)
- On-line (VFI) mode efficiency up to 94% at full load
- Active ECO mode efficiency up to 98%
- Energy Star® 2.0 certified
- Controllable and programmable output sockets
- Integrated solution with batteries and electronics
- External battery cabinets auto-detection
- Operates at full power up to 40ºC (up to 50ºC with derating) Intelligent Communication ready
- Safety Agency Approved Category B IEC 61000-4-5 Surges/Lightning protection capability)
Specifications
| Rating | 750VA/750W |
---|
Input | Rated Voltage | 230VAC |
---|
| Rated Frequency | 50/60Hz |
---|
| Frequency Range | 40 to 70 Hz |
---|
| Power Factor | ≥0.99 |
---|
Output | Nominal Voltage | 200/208/220/230/240 VAC |
---|
| Waveform | Sine wave |
---|
| Inverter Overload Capability | >200% minimum 250 mS, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds |
---|
| Efficiency in Online Mode | Up to 93% |
---|
| Inverter Bypass | Up to 98% |
---|
| Output Receptacles | 8x EN60320/C13 |
---|
Internal Battery | Rated Voltage | 36Vdc |
---|
| Charger Current | Nominal 2.2 A; Maximum 8A |
---|
| Type | Valve-regulated, non-spillable, lead acid |
---|
| Quantity x V x Rating | 3 x 12V x 9.0Ah |
---|
| End Cell Voltage | 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, can be selected by PARAMSET) |
---|
| Floating Voltage | Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell |
---|
| Battery Voltage Range | 30 Vdc to 42.3 Vdc |
---|
| Internal Battery Backup Time (Approximate) | 10% Load Capacity: 92.5 mins 20% Load Capacity: 47 mins 30% Load Capacity: 29 mins 40% Load Capacity: 20 mins 50% Load Capacity: 15 mins 60% Load Capacity: 11.5 mins 70% Load Capacity: 9.5 mins 80% Load Capacity: 8 mins 90% Load Capacity: 7 mins 100% Load Capacity: 6 mins |
---|
General | Operating Temperature, °C | Full power up to 40 ºC (up to 50 ºC with derating) |
---|
| Storage Temperature, °C | - 15 to + 40 |
---|
| Relative Humidity | 0 to 95% non-condensing |
---|
| Operating Elevation | Up to 3,000 m at 25°C without derating |
---|
| Audible Noise | <46 dBA, at 1 meter from sides, <43 dBA, at 1 meter from rear |
---|
| Safety | IEC62040-1:2008 version, GS mark; CE: UL1778 5th Edition and CSA 22.2 No 107.1 |
---|
| EMI/EMC/C-Tick EMC | EN 62040-2:2006; EN 61000-3-3:2013; EN 61000-3-3:2013 |
---|
| Transportation | ISTA Procedure 1 A |
---|
| Surge Immunity | ANSI C62.41 Category B IEC 61000-4-5 Surges/Lighting |
---|
| Dimensions (mm) | 400 (w) x 430 (d) x 85 (h) |
---|
| Weight | 16.5kg |
---|