Vertiv UPS GXT5-5000IRT On Line 5000VA UPS
Dove Code:
UP4518 |
Manufacturer:
GXT5-5000IRT5UXLN
Overview
The Vertiv™ Liebert® GXT5™ UPS is an online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system.
Warranty
36 Month Return to Base Warranty
Features
- Designed for high availability
- User-Friendly Operation and Installation
- Longer Life Time and Run-Time of Batteries
- Optimized Energy and Capacity Management
- Seamless Connectivity
Specifications
Dimensions 7 Weight | Dimensions | 430 (W) x 630 (D) x 217 (H) |
---|
| Weight | 70.8kg |
---|
Input AC Parameters | Operating Frequency | 50 or 60 Hz |
---|
| Factory Default Voltage | 230VAC |
---|
| Operating Voltage Range | 176 to 288 VAC (100 to 176 VAC with power derating)
|
---|
| Maximum Allowable Voltage | 288 VAC |
---|
| Input Frequency | 40 to 70 Hz |
---|
Output AC Parameters | AC-AC Efficiency | 95% |
---|
| User-configurable Voltage | 200/208/220/230/240 VAC |
---|
| Factory Default Voltage | 230 VAC |
---|
| Frequency | 50 Hz or 60 Hz, Nominal |
---|
| Waveform | Pure Sinewave |
---|
| Output Power Connection | Output terminal block |
---|
| Main Mode Overload | >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous |
---|
Internal Battery | Charger Current | 2.25 A (default), maximum 5 A |
---|
| Type | Valve-regulated, non-spillable, lead acid |
---|
| Qty x V x Rating | 2 x 8 x 12V x 9.0 AH |
---|
| Back-up Time at Full Load | 7 |
---|
| Back-up Time at Half Load | 18.5 |
---|
Bypass Protection Limits | Upper-limit Selections | + 10%, + 15%, + 20%; default + 10% |
---|
| Lower-limit Selections | - 10%, - 15%, - 20%; default - 15% |
---|
| Disable-bypass Operation | When the input frequency prevents synchronous operation |
---|
General | Operating Temperature, °C | Full power up to 40 ºC (up to 50 ºC with derating) |
---|
| Storage Temperature, °C | - 15 to + 40 |
---|
| Relative Humidity | 0 – 95% non-condensing |
---|
| Operating Elevation | Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating |
---|
| Audible Noise | <55 dBA |
---|
| Safety | UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013 |
---|
| EMI/EMC/C-Tick EMC | IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI) |
---|
See full manufacturer specifications